5.6. REPLACE GENERATOR SET (Continued).
5. Remove eight self-locking nuts (7), 16 flat washers (8), and eight screws (9) securing the generator
set to the trailer.
CAUTION
Ensure lifting sling (figure 5-3) consists of a suitable spreader bar arrangement to prevent
damage to the generator set housing.
6. Connect lifting device (10).
7. Insert ropes (11) through each of four lifting rings on the generator set.
8. With one person at each rope (11) to steady and guide the generator set (4), lift generator set.
INSTALLATION
WARNING
When lifting the generator set, use lifting equipment with a minimum lifting capacity of 6000
lb. Do not stand under the generator set while it is being lifted. Do not permit generator set
to swing. Failure to observe this warning can result in severe personal injury or death.
CAUTION
Ensure lifting sling (figure 5-3) consists of a suitable spreader bar arrangement to prevent
damage to the generator set housing.
1. Attach lifting device (10) and lifting sling with a minimum lifting capacity of 6000 lb. as shown in figure
2. Insert rope (11) through each of four lifting rings on generator set (4).
3. With one person at each rope (11) to steady and guide the generator set (4), lift the generator set.
4. Guide generator set skids into position on the trailer and lower generator set onto trailer.
5. Position generator set over mounting holes on trailer.
6. Install eight screws (9), 16 flat washers (8), and eight new self-locking nuts (7) that secure generator
set (4).
7. Disconnect lifting device (10) and (11).
8. Route cable W 1 or W2 (1) through power cable sock on front of generator set.
9. Reconnect ground cable to generator set terminal (5) and electrical leads to terminals (6) and tighten
lugs.