1.11. EQUIPMENT CHARACTERISTICS, CAPABILITIES, AND FEATURES.
1.11.1. Characteristics. Two generator sets are mounted on a modified XM1061E1 5 ton, 4 wheel trailer.
The modification to the basic trailer includes generator, a switch box, an accessory box and fire extinguisher
brackets. Refer to TM 9-23 30-376-14&P for detailed equipment characteristics about the XM1061E1.
1.11.1.1. Power Plant AN/MJQ-1612. The AN/MJQ-1612 Power Plant consists of two MEP-806A Generator
Sets, cable storage box and switch box. The generator sets are DOD MEP-806A liquid-cooled, diesel engine
driven units, with a load capacity of 60 kW at 50/60 Hz. Refer to TM 9-6115-645-10 for detailed equipment
characteristics about the generator sets.
1.11.1.2. Power Plant AN/MJQ-1632. The AN/MJQ-1632 Power Plant consists of two MEP-816A Generator
Sets, cable storage box and switch box. The generator sets are DOD MEP-8 16A liquid-cooled, diesel engine
driven units, with a load capacity of 60 kW at 400 Hz. Refer to TM 9-6115-645-I0 for detailed equipment
characteristics about the generator sets.
1.11.2. Capabilities and Features. The generator sets for the AN/MJQ-1612 and AN/MJQ-1632 are mounted
on the same trailer. Electrical outputs are provided in paragraphs 1.11.2.1 and 1.11.2.2.
1.11.2.1. Power Plant AN/MJQ-1612. The electrical output of the power plant is as follows:
ELECTRICAL OUTPUT - 50/60 Hz:
120/208 volts, three phase, 50 Hz .................................................
416 amps
240/416 volts, three phase, 50 Hz .................................................
208 amps
120/208 volts, three phase, 60 Hz ..................................................
344 amps
240/416 volts, three phase, 60 Hz ..................................................
164 amps
1.11.2.2. Power Plant AN/MJQ-1632. The electrical output of the power plant is as follows:
ELECTRICAL OUTPUT - 400 Hz:
120/208 volts, three phase, 400 Hz ................................................
416 amps
240/416 volts, three phase, 400 Hz ...............................................
208 amps
1.12. LOCATION AND DESCRIPTION OF MAJOR COMPONENTS.
Figure 1-3 illustrates the location of major components on the AN/MJQ-1612 and AN/MJQ-1632. Table 1-2
lists the major components of the power plants.